The machine will not start from the platfom control station and the JLG analyzer reads FSW OPEN in the help message menu.

Symptoms

0011 FSW OPEN

Possible Causes

Defective joystick or toggle switch at the platform control station.

Troubleshooting Steps

1. Using the JLG analyzer, scroll through the following menus to the menu item at the end. The menu item should read as stated beside it. DIAGNOSTICS: DRIVE/STEER

A. Verify the Drive Output is showing 0%.

B. Verify the Steer Output is showing 0%.

2. If either Drive or Steer output is showing a percentage other than 0%, the Drive/Steer joystick is defective and will need replaced.

3. Using the JLG analyzer,scroll through the following menus to the menu item at the end. The menu item should read as stated beside it. DIAGNOSTICS: BOOM FUNCTIONS

A. Verify that all boom function outputs are showing 0%.

4. If any Boom Function output is showing a percentage other than 0%, the function switch or joystick is defective and will need replaced.

Suggested Tools

  • JLG Hand Held Analyzer